Calendar
Expert knowledge
Favourites
Your account
Shopping cart

Raycap 60 mm busbar type I+II – free from leakage current – ProTec 60 T1-300-3+1-R

Type of manufacturer: ProTec 60 T1H-300-3+1-R
Manufacturer Art. No.: IZ515964000
Art. Nr.: 11905
Pieces per package unit:
  • 1 per pack
  • 20 per carton
  • 480 per pallet
Accessory type: Overvoltage protection
WEEE-Number:
  • DE200136
Prices are only visible to business customers upon successful registration.
Available from stock
Product number: 11905
Prices are only visible to business customers upon successful registration.
Available from stock
Product number: 11905
Description

Raycap 60 mm busbar type I+II – free from leakage current – ProTec 60 T1-300-3+1-R

The Raycap ProTec 60 T1-300-3+1-R is a world first when it comes to lightning current and surge arrester combinations. It has been designed specifically for main distribution boards and 60 mm busbar systems. With a protection rating of IP20 and a robust thermoplastic casing, this device offers reliable protection for TT and TN-S distribution networks. The ProTec 60 T1-300-3+1-R meets the requirements of IEC 61643-11 and EN 61643-11 standards and ensures maximum safety and efficiency in electrical installations.

This item is free of leakage current and can therefore be used in the pre-metering area

 

Product advantages

  • Compatible with TT and TN-S networks
  • Ideal for main distribution boards and 60 mm busbar systems
  • Including remote signaling contact
  • Less time spent wiring and minimized complexity thanks to pluggable concept
  • Enormous time and space savings thanks to simple installation and maintenance
  • Can be used with a wide range of busbar widths and thicknesses: 
    • Thickness: 5, 10 mm (10 mm – by removing the contact element)
    • Width: 12, 15, 20, 30 mm

Technical specifications

  • Overvoltage type I+II
  • Rated voltage AC: 240 V
  • Maximum continuous voltage (AC) (L-N): 300 V
  • Highest continuous voltage (AC) (N-PE): 305 V
  • Rated leakage surge current (8/20 µs) (L-N)/(N-PE): 20 kA / 40 kA
  • Maximum leakage surge current (8/20 µs) (L-N)/(N-PE): 50 kA / 65 kA
  • Protection level (L-N)/(N-PE): 1500 V / 1500 V
  • Sequential current extinguishing capacity (N-PE): 100 A
  • Overcurrent protection (max): 315 A gG
  • Protection category: IP20
Raycap 60 mm Sammelschiene leckstromfrei
Raycap 60 mm busbar type I+II – free from leakage current – ProTec 60 T1-300-3+1-R
Available from stock